5747 E. Santa Ana Canyon Rd. (2)
www:..anaheim.nel
City of Anaheim
DEPARTMENT OF PUBLIC WORKS
December 28, 2004
REVISED 05-16-2005
Mr. Jack Jakosky
503 32ND Street, Suite 200
Newport Beach, California 92663
SUBJECT: NEW COMMERCIAL CONSTRUCTION (D-185)
5747 E.Santa Ana Canyon Road
BLD2004-04238
Dear Applicant:
The Public Works Department has reviewed the plans for your building permit
application at the subject location for conformance with City requirements associated
with street right-of-way, traffic, sanitation, street improvements, sewer, drainage,
grading, and land subdivision. The information in this letter is intended to help you to
complete your building project with as little inconvenience as possible.
STREET RIGHT-OF-WAY
No Street Right-of Way dedication is required for this project.
TRAFFIC AND TRANSPORTATION
The following traffic related fees are due. The fees will be collected at the Building
Division counter prior to issuance of your building permit.
Transportation hnpact and hnprovement
Traffic Signal
Traffic Santa Ana Canyon
Eastern Transportation Corridor
$ 4,386.00
$ 2,044.00
$ 2,313.00
$ 11,352.00
If you need additional information concerning these fees, contact Mr. Alfred Yalda in the
Traffic Engineering Division at (714) 765-5183.
SANITATION
Trash storage areas shall be provided and maintained in a location acceptable to the
Public Works Department. A plan for trash storage, collection and a plan for recycling
shall be submitted and approved prior to issuance of building permit. An on-site trash
truck turn around is also required. Contact Ms. Dora Monzon in Streets and Sanitation
Division at (714) 765-6836 if you have any questions concerning these requirements.
P.O. Box 3222
Anaheim-, California 92803
TEL (714) 765-5176
fAX '17141765-5225
.
,.
r,
200 S, ANAHEIM BlVD.
(714) 765 - 5153
CITY OF ANAHEIM
PLAN CHECK RECEIPT
r BUILDING PERMIT NO.: BLD2004-04~
DATE:
TYPE OF PERMIT:
JOB ADDRESS:
LEG RIPTION:
APPLICANT:
11/23/2004
NEW COMMERCIAL CONSTRUCTION
5747 E SANTA ANA CANYON RD
DOMINGUEZ ESTATE LOT 4 POR OF LOT
437
QUARTER SECTION: 185
OWNER INFORMATION:
CONTRACTOR INFORMATION:
ARCHITECT/ENGINEER INFORMATION:
CARLILE COA TSWORTH
2458 DUPONT DR.
IRVINE, CA 92612
Imperial Properties
2424 SE Bristol St #200
Newport Beach, CA 92660
JOB DESCRIPTION:
VALUATION:
New 7800sf retail shell only bldg
360,000.00
Construction Types:
VN
Occupancy Groups:
B
Fire 8prinklered?
Number of Stories
New I Additional Area:
Fees paid for Permit:
Plan Check. New Construction
Total:
2.151.38
2,151,38
YES
1.00
7.800.00
To obtain Plan Check Review results through our Automated Response System, please call the following number and select
the following options:
(714) 765-4626
Press (2) Permit Functions
Press (1) Permit Plan Review
Press (1) for BLD. Enter the 9-digit PermiUPlan Review number
Your plan check should be completed by the City DevelopmentTeam by 12/2112004. The Plans Examiner assigned to
your project will contact you if plans are ready before thl! noted ,date.
Founded in 1857, the City of Anaheim is one of the nation's premier municipalities and California's 10th most populous city. As the oldest and largest
city in Orange County, Anaheim covers 50 square miles, with nearly 330,000 residents and 2,100 City employees. The municipal corporation's
annual budget is $960 million and boasts world-dass companies such as Boeing, Carl Karcher Enterprises, Disney, L.J Communications, MTI
Technology and Pacific Sunwear. Annually, the City of Anaheim also welcomes millions of ViSHOIS, truly making it a place where the world comes to
live, work and play. C CJ (0 '3.00 'I... 0 'I ,., ,
pL~~ : trlJl'bIJ fl"lhHl M'Z.
,1
",
I.
<-"i<.:~,....~.>. .,..:.,-;,:;.:..;:,,:,~.:,;... ,>,:
""'irC,"'"''
f>;'.'>>';";"c.'" ,~'",":,
- .,,,, 'j~'.:,... /
-;,- .. "~', ';.:.;..:..,y..,:_~";,,,,,,,,,.,.,,,.,,,,,,,; '"'~l'~'"",~.; .7.-':>{
.:,'.. '~;_'.' ,,,,,,:h: '.~'<'f." . ,',,<,1'';'';- ..,)_J..~'~~">""'!_':-': '~i.;> .. '~_:< .',"
;:',':i: '<">;:..
,,:'~;..~_.;;.iti(.",t-"t"-~' ,~:,,,,_.,'
( .
~'W'Mt'''ll,.I'''.'';~i.':;;'::::..~\W;''""
:,':.,',
i,,''''';''
.. ~,,; ",'.,;,'
.. ,.c, ;'''-,-,,-,:.~ '".,'
,'r, '-;;.,\.,.;.
'_\';:i:i ., ;.~,.' ...... " .,.,,;,"0 ..
,;.:~/ti:"
'\. .....6 \'t po L" ~t; A to.",., ~''''>
fJ"" ~ ( ..,,) .'. It" '",) '''' '<II lkfft L: .,.;J
t':,-~>",..:;~..:.,". ';'~::"'-;";"~'.':1..);"i,~~.,~;.'f~,,;.'.,~;'1''''FI!l.~~,,:... .:>l";'~";liWIA;;-";''(.i:'~''"''',.~~':f,:,,'.o:~,tg
4l::'" <"!l, 0"" , ,,~ ."t,., 'iI',,-
.,,"~ ""W'f'\ \ ,,~\ ~.....".,;\
,"",,"'.;:~<~...;,~
...,"~'-;,.." '. ;'.,',,.!:c,."/<,' c ....;,.;.,';"...".,.i'l:'_"~~.tI\.,:,"',....-...,"'._.~..'l<.~.."',,.."'..._,,_,;.....",. ";'>"\;.',,",.. '-"'k,'''',o,
~~ .,,\,. J..",~"". ~ 1M. ..J'th It.. ,...., ~. ~;l
'''';,p, ,..-,l:! ~d . tr'-'jft'i.;;,.. 't"'i"... ~.~\if ':'
..
.. . it .
PUBLIC WORKS DEPARTMENT FEES
. BUILD # D~ _ () ~ '1. '!;:tRAFFI~ENGINEERlNG FEES--
PROJECT SITE: 1$'" I.fl E. . JfP.6
SIZE: 7 iO (7 SF' . !
~ S !i!
~~RAFFIC SIGNAL FEE : !' !
279-412-F724-3017
TE# "2-
tr>< S II
~.
-== ~.()W
,i:g'!RANSPORTATIONIMPACT AND IMPROVEMENT FEES: ) .Ii
278-412-F724-1818 .:;::::;oS- e;; e;; ><(2. 0..3 - · 70' _ /a.3'
-
~RAFFIC SANTA ANA CANYON FEE: '/ 8' d 0 )( , 7 t> I d5. . cJ
278-412-F724-2001 . ~ ~S.4 b8'
~ASTERN TRANSPORTATION CORRIDOR FEE:
101-412-F724-6704 7tr 0 0 x~. Q4 =
o
~ (;" 83 z.-,
COMMENT:
REVIEWED BY: ALFREDYALDA (714) 765-5183
A,\
DATE: \ \-Z~-OY
--DEVELOPMENT ~SKEES--
RlGHTOFWAY ~I:@- REVIEWEDB .. DATE: \l!~)rrlj
o ~LD ZONING CODE (i.e. in plan check or entitlement prior to July 8, 2004) jl.. -\
)2f NEW ZONING CODE
DEDICATION ~
CREDIT
.
STREET IMPROVEMENTIREPAlR tV/A
SEWER CONNECTION FEE N /4-
CITY SEWER ASSESSMENT N IA
ACCT #
ACCT #
DRAINAGE ASSESSMENT FEE filA
GRADING:Q~ 'Lo64 _ 0) L'L'} D
WATER QUALITY MANAGEMENT PLAN (WQMP) o"lk?oo ~_ f)D I~t
ACCT #
LAND SUBDIVISION: C Pc.. '2..9 0 Lr_oDo S ~
REVIEWED BY:
t-> v'f -
lLZ-1- C>~
(
www.anaheim.net
City of Anaheim
DEPARTMENT OF PUBLIC WORKS
December 28, 2004
Mr. Jack Jakosky
503 32ND Street, Suite 200
Newport Beach, California 92663
SUBJECT: NEW COMMERCIAL CONSTRUCTION (D-185)
5747 E.Santa Ana Canyon Road
BLD2004-04238
Dear Applicant:
The Public Works Department has reviewed the plans for your building permit
application at the subject location for conformance with City requirements associated
with street right-of-way, traffic, sanitation, street improvements, sewer, drainage,
grading, and land subdivision. The information in this letter is intended to help you to
complete your building project with as little inconvenience as possible.
STREET RIGHT -OF- WAY
No Street Right-of Way dedication is required for this project.
TRAFFIC AND TRANSPORTATION
The following traffic related fees are due. The fees will be collected at the Building
Division counter prior to issuance of your building permit.
Transportation Impact and Improvement
Traffic Signal
Traffic Santa Ana Canyon .
Eastern Transportation Corridor
$ 10,366.00
$ 4,088.00
$ 5,468.00
$ 26,832.00
If you need additional information concerning these fees, contact Mr. Alfred Yalda in the
Traffic Engineering Division at (714) 765-5183.
SANITATION
Trash storage areas shall be provided and maintained in a location acceptable to the
Public Works Department. A plan for trash storage, collection and a plan for recycling
shall be submitted and approved prior to issuance of building permit. An on-site trash
truck turn around is also required. Contact Ms. Dora Monzon in Streets and Sanitation
Division at (714) 765-6836 if you have any questions concerning these requirements.
P.O. Box 3222.
Anaheim, California 92803
TEL (714) 765-5176
FAX (714) 765-5225
l
\
.
Page 2 of2
Date: December 28, 2004
SUBJECT: New Conunercial Construction (D-185)
5747 E.Santa Ana Canyon Dr.
BLD2004-1l4238
STREET IMPROVEMENTS
Any improvements damaged prior to or during construction at your site must be repaired
prior to clearance for certificate of occupancy (reference Section 18.40.060.030 of the
Anaheim Municipal Code).
SEWER & DRAINAGE
No City of Anaheim sewer and drainage assessment fees are applicable to this project
WATER OUALITY MANAGEMENT
A Water Quality Management Plan (WQMP) (OTH2004-00l86) has been submitted to
Public Works Division and is currently under review. WQMP Plan must be approved
prior to issuance of building permit.
GRADING
Grading plan (GRA2004-02290) has been submitted to Public Works Division and is
currently under review.
LAND SUBDIVISION
Certificate of Compliance (COC2004-00053) has been submitted to Public Works Division
and is currently under review.
If you need additional information conceming street improvements/repair, sewer and
drainage fees, water quality management, grading, and/or land subdivision please contact
the undersigned at (714) 765-5100 extension 5816.
Respec~ .
/V~-
Adrian V. Pauna
Principal Engineering Aide
o FILENAME \p A:\MRY ACB.docO
c: GaT)' E. Johnson, Director of Public Works and City Engineer
Carlile Coatsworth Architects, Inc.
2458 Dupont Drive, hvine, CA. 92612
Chris Lee, Building Plan Check Supervisor
Doug Faulkner. Zoning Plan Check Supervisor
File
DATE:
FROM:
TO:
FAX NO.:
CITY OF ANAHEIM, CALIFORNIA
Planning Department
FACSIMILE TRANSMISSION
TELECOPIER NUMBER (714) 765-5280
December 15, 2004
Douglas E. Faulkner, Associate Planner
Zoning Plan Check Supervisor
Deb Sands
Carlile Coatsworth Architects
(949) 833-1140
NUMBER OF PAGES (INCLUDING THIS PAGE): 9
COMMENTS: Fire Dept. Corrections and Police Dept. Recommendations
for BLD2004-04238 at 5747 E. Santa Ana Canyon Road.
PLEASE CALL (714) 765-5139 IF ANY PAGES ARE NOT RECEIVED.
THANK YOU!
Con f i rma t i on Repo r t - Memo ry Send
Job number
Date
To
Document pages
Start time
End time
Pages sent
Status
Job number 815
Time
Tel line
Name
12-15-2004 11:5lam
815
12-15 11 :50am
919498331140
009
12-15 11 :50am
12-15 11 :5lam
009
OK
*** SEND SUCCESSFUL ***
~<-
0'" ",:Q:
€ '\
. .
- .
DATE;
FR.<>l'\I.I:;
TO:
FAX NO.:
crrv OF ANAHED04.. CALIFOlU-U.A.
P!.anDiAg Dep~Dt:
FACSIlVULE TRANSl\USSION
TELECOPIER. ~ER. (714) 765-$280
D~exnber '15.. 2004
no.....glas E. Faulk..er.. A.ssocia'te PJ_lI:lUD.er
ZoulD.a: P).au Cheek. Saperv150r
Deb Sands
CarUle Coats'ftl'ort:h,Archl1=ec:u
N'O'l\oot:bER. OF PA.GES (INCLUDIN'G T~S PAGE): 9
(949) 833-1140
C<>~NTS: Fire Dep't. Corrections aDd Police Dept. R.ecoI'ftJnC!:n<<J.atioDs
:f'or DLD2Q04-04238 a'C 5747 E. Santa Ana Canyon R.oad.
PLEASE CALL (714) 76$-5139 ]:F .ANY PAGES ARE NOT REC'ErvED..
THANK your
www.anaheim.net
City of Anaheim
ANAHEIM FIRE DEPARTMENT
~
-
E,ltlERGtlIC'iSDYIW
Plan Check # n l~ 'U ~4 .- 1,,12 q/
Address: ~741 t. rAJJf;f. ANt. c~f'"
Plan Reviewer:' Todd Rudaitis
Phone: (714) 765-4067
Date:
Occupancy:
Square feet:
!L.J.q.
Ig
1.,r- 0
ALL FIRE DEPARTMENT REQUIREMENTS MARKED "NOT SHOWN"
SHALL BE INCORPORATED AS A VERBATIM NOTE ON THE PLANS'
UNLESS OTHERWISE INDICATED.
Not
Shown Shown
1. All required fire hydrants shall be installed, tested and
accepted prior to construction. CFC 901.3
Required fire flow: GPM @ 20 psi. CFC A.Ill-A
2. Fire apparatus access roads shall be designed and
maintained to support the imposed load of 70,000 Ibs., and
shall be provided with an all.weather surface. Such roads
shall be installed prior to construction. CFC 902.2.2.2
3. 1 Provide an approved automatic fire sprinkler system in
accordance with NFP A 13 . Plans for the
installation of the sprinkler system shall be submitted for
approval to the Anaheim Fire Prevention Division prior to
installation. CFC 1003
4. Provide an approved class standpipe system.
Submit plans or approval to the Anaheim Fire Prevention
Division prior to installation. CFC 1004
S. Plans showing underground piping to on-site hydrants and
-
sprinkler systems shall be submitted to the Anaheim fire
Prevention Division prior to installation. CFC 901.2.2.2
6. L Show the location(s) of all fire hydrants within 1/) &
feet of all portions oflot frontage. CFC A-m-B
7. The fire sprinkler system shall be monitored by an
approved central station, remote station, or proprietary
supervising station when the number of sprinklers are 100
or more in all occupancies not normally occupied 24-
hours a day, or provided with 24-hour guard service.
CFC 1003.3
Fire Prevention Division
201 S. Anaheim Boulevard, Suite 300
Anaheim, California 92805
TEL (714) 7654040
FAX (714) 7654608
G:\Fire Prevention\FORM$\Plan Check Corrections Form.dot
Pagelof3
8.
9.
10.
Shown
15.
16.
17.
18.
19.
Not
Shown
.~
....
Provide an approved manual/automatic fire alarm system. Plans for
. the fire alarm system shall be submitted to the Anaheim Fire
Prevention Division prior to installation. CFC 1006
Provide an approved fire suppression system for the kitchen hood.
Plans for the fire suppression system shall be submitted to the
Anaheim Fire Prevention Division prior to installation.
CFC 1005.2.2
v
Provide minimum 2-A: 10-B:C flre extinguishers. Location(s) to be
determined by Fire Department Inspector. CFC 1002.1
Provide occupant load calculations and posting of room capacity.
CFC 2501.16.1
Provide a seating plan showing all aisle dimensions in accordance
with CFC 2501.10.
The use of combustible decorative materials shall comply with CFC
Section 1103.3.3.
Storage of combustible materials in closely packed piles or on
pallets, in racks, or on shelves where the top of storage is greater
than 12 feet in height shall comply with CFC Article 81.
Cross-hatch or shade, on the site plan, the required 20 foot wide
unobstructed fire lane to within feet of all portions of the
exterior walls. Fire lanes shall be posted as "Fire Lane - No
Parking" in accorQance with Anaheim Fire Department
requirements. CFC 902.2
Provide a signed owner's statement of intended use for the
warehouse. CFC Article 81
Complete and return the attached chemical classification packet. If
no hazardous materials are to be store, used or handled in the
building, a statement from the business owner or property manager
will be accepted in lieu of the classification packet. CFC Article 80
Storage, use or dispensing of hazardous materials, as defined by the
Fire Code, shall comply with CFC Article 80.
Installation or removal of aboveground/underground storage tanks
shall be approved by the Anaheim Fire Department under separate
review.
G:\Fire P(even~cn\FORMS\?\arl Check Ccrrectons Form.cot
Pa~a2ol3
ANAHEIM POLICE DEPARTMENT
OPERATIONS DIVISION
Plan Check Recommendations
T6: Ii/ /4
.
Date: /J -7 -olf
Case #: :/VDl( - 0 '-1;2 :> i'
Location: 57'-[7 6. SfJrAfToA
From: Susie Schmidt
Crime Prevention - West District
714-816-6584
sschmidt@anaheim.net
Building counter hours:
A-N~ C--"lN1otJ ~I:>
The Anaheim Police Department Crime Prevention Unit recommends that the following
crime prevention measures, as noted, be considered for the above project.
SECURITY MEASURES:
~ Business to be equipped with alarm system (silent or audible)
~ !:!:.~ide co.mprehensive security alarm system for the following:
~y'erimeter building and access route protection.
kjlj.igh valued storage areas.
L31nterior building door to shipping and receiving area.
o Perimeter fence and security gating.
g/ Complete Burglary/Robbery Alarm permit application, Form APD 516, available
at the Police Department front counter.
. .
~ Closed Circuit Television (CCTV) security cameras are recommended, with the
following coverage areas:
~!-Obby entrances QrEXterior entrance
ITE!uilding perimeter g1)tairwell
[;}'Shipping and receiving areas 0 Interior hallway
o Parking lot 0
if If security cameras are not monitored, signs indicating so should be placed at
each camera.
~ CCTV monitors and recorders should be secured in a separate locked
compartment to prevent theft or tampering of the tape.
~ Recorded CCTV tapes should be kept for a minimum of 30 days before being
recorded over.
.-
g CCTV tapes should not be recorded over more than 10 times per tape.
DOn-site security personnel (uniformed recommended).
ADDRESSING:
g/ Address numoers shall be positioned so as to be readily readable from the street.
Minimum number height of 12" recommended. Numbers should be illuminated
during hours of darkness.
~ Businesses with rear entrance doors shall be numbered with the same
address numbers or suite number, minimum height of 4" recommended.
~ Rooftop address numbers for the police helicopter. Minimum size 4' in height
and 2' in width. The lines of the numbers are to be a minimum of 6" thick.
Numbers should be spaced 12" to 18" apart. Numbers should be painted or
constructed in a contrasting color to the roofing material. Numbers should face
the street to which the structure is addressed. Numbers are not to be visible
from ground level.
g/ Industrial, commercial, institutional or office buildings shall have clearly marked
doors with numbers corresponding to the alarm zones, if any. The identification
of alarm 20ne coverage will assist responding police and security units in faster
identification al}d apprehension of potential suspects, if any.
~ Each different unit within the building shaH have its particular address displayed
on its front and rear doors or directly above the front and rear doors.
DOORS:
~ All exterior doors to have adequate security hardware, e.g. dead bolt locks.
Peephole, or similar viewing device, should be installed in the 1Z~&tdoor.5
rr
~
B'
The locks shall be so constructed that both the dead bolt and deadlocking latch
can be retracted by a single action of the inside doorknob/lever/turnpiece.
Overhead roll-up doors shall also be secured on the inside that the lock cannot
be defeated from the outside and shall be secured with a cylinder lock or padlock
from the inside.
WINDOWS:
o Bullet resistant glass at attendant's kiosk.
2
<
if Windows accessible from the side and rear and not viewable from the street shall
consist of rated burglary resistant glazing or its equivalent. The type of glazing
recommended is the lock wrap type that attaches to the frame.
D Large store/business display windows shall consist of burglary resistant glazing
or its equivalent.
ROOFTOPS AND OPENINGS:
~ All glass skylights on the roof of any building shall be provided with:
1. Rated burglary resistant glass or glass-like acrylic material.
or 2. Iron bars of at least y," round, or 1" by y." flat steel material, spaced no more
than 5" apart under the skylight and securely fastened.
or 3. A steel grill of at least 1/8" material under the skylight and securely
fastened.
~ All hatchway op~nings on the roof of any building shall be secured as follows:
1. If the hatchway is of wooden material, if shall be covered on the outside with
at least 16-gauge sheet steel or its equivalent attached with screws.
2. Outside hinges on all hatchway openings shall be provided with non"
removable pins when using pin-type hinges.
~ A Knox box shall be installed at hatchway to allow Police/Fire access to interior.
~ Exterior roof access ladder should be eliminated or moved into the interior.
Exterior ladders allow easy roof access for criminals, etc. This ladder should be
relocated within the building main resident tenant space.
~ All air duct or air vent openings exceeding 8" x 12" on the rooftop or exterior walls
of any building shall be secured by covering the same with either of the following:
1. Iron bars of at least Y:!' round, of 1" by y." flat steel material,
spaced no more than 5" apart and securely fastened.
or 2. A steel grill of at least 1/S" material and securely fastened.
3. If the barrier is secured to the outside of the structure, it shall be secured with
galvanized rounded head flush bolts of at least 3/8" diameter on the
outside. ..
LIGHTING:
~ Monument signs and addresses shall be well lighted during hours of darkness.
~ Premises, if closed for business after dark, must be sufficiently lighted by use of
interior night-lights.
~ Minimum recommended lighting level in all parking lots is one foot-candle, with a
maximum to minimum ratio no greater than 15:1.
3
r
o Minimum recommended lighting level for covered portions of all parking garages
is five foot-candles, with a maximum to minimum ratio no greater than 10:1.
~ Adequate lighting of parking lots and associated carports, shipping and receiving
areas, driveways, circulation areas, aisles, passageways, recesses, and grounds
contiguous to buildings shall be provided with lighting of sufficient wattage to
provide adequate illumination to make clearly visible the presence of any person
on or about the premises during the hours of darkness and provide a safe,
secure environment for all persons, property and vehiclesonsite.
g/ All exterior doors shall have their own light source which shall adequately
illuminate door areas at all hours to make clearly visible the presence of any
person on or about the premises and provide adequate illumination for persons
exiting the building.
LANDSCAPING:
~ landscaping shall be of the type and situated in locations to maximize
observation while providing the desired degree of aesthetics. Security planting
materials are encouraged along fence and property lines and under vulnerable
windows.
~ Trees should not be planted close enough to the structure to allow easy access
to the roof, or kept trimmed to make climbing difficult.
VISIBILITY:
rr Doorways should not be recessed to the extent that a place is created for a
person to stand and go unobserved.
if Interior hallways should provide good line of sight for proper CCTV surveillance.
~ Stairwells should have convex mirrors installed on the landings to allow visibility
of landing and next flight of ~tairs.
.0 Elevator cabs should have convex mirrors installed to allow visibility of the
interior of the cab from outside the elevator door.
~ Trash enclosures should not block visibility of doors or windows or be located
close enough to the structure to provide access to the roof.
4
SIGNAGE/PARKING LOT:
~ "No Trespassing 602 G) P .C." posted at the entrances of parking lots and located
in other appropriate places. Signs must be at least 2' x l' in overall size, with
white background and black 2" lettering.
~ All entrances to parking areas shaH be posted with appropriate signs per
22658(a) C.v.C., to assist in removal of vehicles at the property
owners/managers request.
o Parking lots and parking structures shall include controlled access points to limit
ingress and egress.
o Parking garages should have emergency stations with two-way communication
capability to Security/Police at stairway landings and appropriately spaced
throughout the structure.
o Parking garages should have roll up gates at all entrances and exits to allow
closing of the garage when business is closed.
~ Marked parking spaces for company Presidents/CEO's should be eliminated for
safety reasons.
FENCING/BARRIERS:
GY
~following installations should be considered:
L':1 Wrought iron fencing and gating with keyed access.
o Chain link fencing and gating.
o j;\lock walls.
[3'Oecorative cement planter barriers.
~Control access to high vaiued storage areas.
Q1::ocked cages, rooms or, safes,
o Shipping and receiving door screens.
o Bullet resistant enclosures with pass through for pick up and delivery.
o Interior man-trap enclosures to .secure and separate shipping and receiving
areas during actual shipping and receiving.
LLANEOUS:
File Emergency Listing Card; Form APD-281, available at the Police Department
front counter.
5
o Other problems unique to this project:
6
'" ~ ",
Please fill In th~ following boxes based on the activities that wlll be performed on site during the term of the building permit for
which you are applying.
There will be no:
[J 'Soil Movement (I.e. earthwork, excavJtion, etc.].
[J Uncovered materials (dirt, sand, fertilizer, etc.] that could be carried offsite by wind or rain.
[J Exterior mixing of cementaceous products onsite (concrete, mortar, stucco, etc.].
If all three boxes are checked, the applicant Is exempt from NPDES reiated storm water inspection requirements.
PLAN CHECK SUBMITTAL DATE: \\ In/a4-
PROJECT ADDRESS: 5747 t::. <;'At-.(\A ANf'... ~t-rY<DN Rn.
. DESCRIBE WORK TO BE DONE: ~\t=vv ~D \SV"!:\--~\--\~
VALUATION OF PROJECT: $ ""$<.,= ,0=
OWNER/TENANT: ARCHITECT J ENGINEER OR RECORD:
Name: -S.LI.\Z<:::>SI,l.Y -PR""i"~~5 Name: CA1Z.~\.:B: ( ~A,<;~~...A=\(~"'a5
&=3 -~~o '::>\ , "3~,= ?DO Z45'(3 DVIbN1:..D_R.
Address: '" to. ""_~.,.. \:>, t= ,.<- ..\ I (A. "'l<.(.,<:,"3 Address: TRv:tl-lt:;
Phone Number: <""'>4-">) Cc73- 0500 Phone Number: l~4'}) 2;33- ~.'}.3..D
APPLICANT: C( A<p...c~tt,,,,,,,,~ CA license Number: 0\4'3 e~
Phone Number: ~Oj4~') 'EB"3 - \ ~'3o Expiration Date: ' ~B '200'5
I',"""';' ,': ," ,:.,J " ' , ' ,PROPERTY INFORMATION f",,'''.-::',. ::c. ':':<',
Current Use: Proposed Use:
Current Occupancy: ,Proposed Occupancy: R"", At:!.... St-dRF:. -<;
Current Square Footage: New Square Footage: 7800
Type of Construction: RemodellTenant Improvement Sq. Footage.:
Fire Sprinklers? I .'
,
Current Codes in EFFect:
2001 CaliFornia Building Code
2001 CaliFornia Plumbing Code
2001 California Mechanical Code
1999 National Electrical Code
City of Anaheim Ordinances
H,IClh:fll-':ll0j~.O~~l"lIr ^?~lICA;:ONJ,,,
( 'l
~
r'
CERTIFICATE OF COMPLIANCE
PAYMENT OF SCHOOL FACILITY FEES
ORANGE UNIFIED SCHOOL DISTRICT
726 W, Collins, Orange, CA 92867
(714) 628-4500
Developer/Applicant Name:
Address:
Canyon Plaza LLC
503 32nd Street Suite 200
Newport Beach, CA 92263
Phone: (949)673-0500
Owner Name:
Address:
same
Phone:
Address/Location:
Type of Project:
Lot #:
Tentative Tract #:
No. of Dwelling Units:
5747 E. Santa Ana Canyon Road - Anaheim, CA
New-Commercial APN#:
~ Single Family
o Multi Family/Condos/Apt.
Total Square Footage:
Multiplied by Applicable Fee:
Other:
$2.24
Applicable Fee Level: ~ 1 0 2 0 3 0 4
Total School Facility Fees:
Total School Facility Fees:
Total Square Footage:
Multiplied by Applicable Fee:
6000
$0.36
Total School Facility Fees:
$2,160.00
~ NO 0 YES
REASON:
The above representations as to square footage are true and correct. Developer/ Applicant agrees that if it is
later determined that such representations are not true, then this Certificate of Compliance shall automatically
terminate and the appropriate City/County all be notified.
Developer/Applicant Signature:
This certifies that the above named Developer/ Applicant has paid school faCility fees in compliance with
Education Code Section 17620 et. seq. an~ve.rnment Code Secti n 65995 et. seq.
Date: 5116/05 Name: !!-:-;.. Title: Administrative Secretary
NOTICE: The 90-day period in which you may protest t e fee des lbed herein will begin on the date this fee is paid. However. if the fee
was imposed by the City or County as a condition of approval for your project, and you have received the requisite notice, the 9D-day
protest period began at the time your project was approved by the City or County.
certificate of compliance
~,:::t.v n?_ ''JdJltf
,
-: ~;-- -',-
tr.:...
B
-'I-'I'
Doorn
00)
I>- .
UOCl!
OOZOl
O"'tl
wI
iI' . w~
ZZC!J
=>.'._"'""'-.2
0'"
UJ',.q,CC
(D~O
Z
'"
0:
o
........ -.- - -..
RECEIVED FROM
. BUD
c(
Z_.J~O..-
,'/
DOLLARS $
AMI OF
ACCOUNT
AMI PA ...., t
BALAN~E
DUE
...~
BY
TYPE OF PERMIT
New Commercial Construction
'CITY'
ElM
BUILDI"'.G DIViSION
, 200 s. ANAHEIM' BLVD.
(714) 765.5153
INSPECTION REQUEST LINE:
(714) 765 - 4626 "
CENSUS CODE: 437
QUARTER SECT)ON:1B5
BUILDING PERMIT,NO. , SLD20(l,4-04238,
DATE: 5/1612005
JOB ADDRESS: 5747 E SANTA ANA CANYON RD
LEGAL DESCRIPTION: DOMINGUEZ ESTATE LOT 4 POR OF LOT
APPLICANT: MARK NORTON
OWNER INFORMATION:
'rrperial Properties
2424 SE Bristol 51 #200
Newport Beaph, CA, 92660
,
CONTRACTOR INFORMATION: ARCHITECT/ENGINEER INFORMATION:
PATTERSON CONSTRUoTiON COMPANYCARLlLE COATSWORTH ARCHITECTS
l '. . .
235 E BROADWAY #3'06 ' '. , ' " '2458 DUP.oNT DR., '
LONG BEACH CA908G2 OI~O IRVINE, CA 92612
BUSINESS PHONE: 56262414,129
JOB DESCRIPTIONNew 600051 relail shell only bldg :
. . r
VALUATION: ,360,000.00 ':
, .~
PROCESSED BY: ENO
, OWNER-BUILDER DECLARATION,
I hereby affirm under penalty of perjury that' am ej(empt from the COl)tractor'~ License Law tor the following reason (S~c. 7031.5 Business and
Prof~ssions CodE!: any-city or county which requires: a permit' to construct~ alte:r, improve, ~ernolish or repair any structure, prior to its issu~nce,- also
requires the applicanffor such permit to file a signed statement ttJat he is'iCer;~d-pursuanfto the provisions of the Contractor's I:-icense Law (Chapter
9)(commencing with Section 7000 of Division 3 of the Business and ProfessiOli.s Code) or that he is exempt !herefrom and the' basis for the alle~d .
exemption. . Any violation of Section 7031.5 by any applicar:'t for- a.permi~ SUbil'its the applicant to a civil pena~y of'not mC?re than fiVe hundred doUars
~~ " , " "
o I, as owner of pr?p~rty., or my employeesrwith wages as their' sole c?mpe;1Sation, ~il! do the 'work, and the structure is not intended or offered for '"_
s~le (Sec. 7044 BUsiness and Professions Code:, The Gontracto~'s License ~rv does not apply to an qwner of property who builds or improves
thereon; and who. does sucli work himself or herself or through his or her own'9.mployees', provided tl:lat,such improvements are not intende~_or
offered for sale. If, however, 'the buikHng or improvement is sold witt} one yea:",of completion, the owner-builder will have the. burden of proving that he.
did not build or improve for the pu",pose of sale). , ".,', . .
o I, as the ownl3r of the prope,rty, am exclusively contracting with licensed Qqntractors to construct the project (Sec.; 7044 Business and Professions
Code: The Contractpr'sLicense Law does not apply to an ow~er of'property~'ho buifds or imp.roves thereon, and who contracts for Such projects with.
~ontractor(s) ,liCensed pursuant to the Co~tra~tor'~ ~icense Law). .-
U I am exempt under Sec. , B& P .c.. for this reason: (.
Date: Owner:
I WORKER'S COMPENSATION DECLARATION
I hereby affirm under penalty of perjury one of the following declarations: 7:
o I ha\~ and will maintain a ce'rtificate of consent ,to self-insu~e for worker'sp'ompensation,.
as provided for by Section 3700 of the Labor Code,for theperformance'ofthe\work fa r ,which
~s permit is issued.' . t!
: I ha, ve and-will maintain worner's compensation i~surance,as requi~d bY;9eOtion'3700 of
, Labor Code, for the performance of the work for which this permit is issUSC'l' My worker's
Compensation insurance 'Carner and poficy are: ' ,
Carrier: STATE RJND ' , Policy ~umber. 046-00081?1
This section need not be completed il the penni! is for one hUndred dollars ($100) Oi' less. '
o I certify'that.in the perfolTnance of the work-forwhichtt)i~ p~rmit is issued:J shaH not
employ any person in any mannerso as to become subject to the workers cori,pensation laws
of Califomia, and agree that if I shOuld become.subject to the WOrker's"corppe1sation', :3
proviSions of Section 3700 of the La . r C e, I " fa' with co with those provisions.
, I
I
LICENSED CONTRACTORS DECLARATION
, hereby affirm under ptlflalty of perjury-that J am
licensed under proVisions of chapter 9 (commencing
with Section 7000) of Divsion 3 of the Bu "ness and"
p'rofes .ons C
5/16/20
Date:
NUMBER
428945
TYPE
TYPE
B
HIC
EXPIRATION DATE
11130/2005
Date: 5/16/2005 ,Applicant:
WARNING' FAILURE TO SECUR WORKER'S COMPENSATION COVERAGE is
UNLAWFUL, AND SHALL SUBJEC , AN EMPLOYERTO CRIMINAL PENAL~IES AND CIVIL
FINES U P TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDI'lION TQ,THE
COST OF COMPENSATION; DAMAGES AS PROVIDED FOR IN SECTJON 3706 OFTHE
LABOR CODE, INTEREST AND ATTORNEY'S FEES, " 'oo~
CONSTRUCTION LENDING AGENCY
I hereby affirm underpenalty of perjury thaUhere is a construction'lending afJe''lcyforthe
performance ofthe work for which this permit ;s issued (Sec.3097.Civ.C): i: .:,-;-
Lender's Information:
Construcion Tvpes:
V. N, ,
OccupancvGroups:
S, ,',',
Fire Sprinklered?
Number Of-Stories
New I Additional Area:
YES
1.
6,000
.~:-,':"'~:"':----,-~_:..., ~.
" ,', ,;, .
"--y ,"-,"
-......~~""'-'---~._'-
.-,"':~-',-,~'~
I certify that I have read this application and 'statethat the- above information is correct. I
agree to oomply with all city. ordinances and state laws relating to building construction, and
hereby'authorize.representives f thiS? city to enter upon th,e above mentioned property for
i specti
Fees paid for Permit: .
Total:
9,996.49
;:7t:- Date: 5/1612005 '
Sighature of .Applicant or Agent
The permit shall expire by limitation and become null,and void if the buDding or
work has not passed final inspection 365, days from the date of permit issuance. A
new permit is required to commence or continue work.
IN"l'ECTION RECORD
. ....... I
. INSPECTOR Ii
INSPECTION . DATE ' '
Temporary Power Pole -,- /" . .' . -I
P'vmbing (OralnlWaSle PipeflC'V..... ,4 ,
Eledrical GrOund Electrode/uter ~to <' ^ /.
SetbacklFormslTrenches' (Footings)
Do not install subfloor or pour floor slab until the' ". . . .
following applicable items have been signed: , .
Plumbing (Water Pipe.Sprinkler valves)
MechaniCal (Groundwork) . .' -,-
Eledrical (Underground Cor\duil) . .
lPle'Slab~ompactlonlMembrane.R8I nt. 111Jo~ '/"""11 ,
UnderpinnIng (Floor Joist/Glrdersl ..,,- ,
Do not cover or concealthe worK below' untlrthe, .
fQllowing applicable items have been Sjg~ ' .
1 st Floor Shear '. '. 1-1"
Fi19sprinkler (Rough) ..... ..' .
2nd Floor Shear' .' .
Roof ISheathinOlOiliDh.liaIntFr';"--;;' '.,-:.. //1i!!!!!f
Masonry (ReinfJB re-Giotitll 1lJ!&:. ~
Rough Plumblr17(To '. .
Rough Meehan f
. Rough 8ectrlC.a1lDrv wall) .. . IC' .
Rough Electrical .' . . . . '., . . i
Framing (Only after Plbg.. Elec., Mech.. and Fire) . ~
Insulation (SoundlEneriiVl '. ....
Do not tape. or plaster 'untillhe fOllowingapp Icable '- .
items have been signed: . ..' '. . .
Drywall --,- . Pr.
.Penetratlons (Fi/8 Rated)Eleetrica/ !
Penetrations (Fire Raled) Mechanical . . -c
PenetratiOns (Fi/8Raled) Plumbing .'
Interior Lath . GENERALITE~
ExterlorLath "1', I
-,-
. .
ExterlOl' 'Plaster (Brown Coat) . . . .'
T -Bar EIClctrlcal . . . .
T-Bar Mechanical .
T -Bar Structural . '. , .
'Sewer .. '.
Water Enginel!rlng Backflow . '.
Water Service ' . .
f
FINAL INSPECTI()NS
Electrical Final
Plumbing Final
Mechanical Final
Gas .Test
Engineering/Grading Final 765-5126
Firl!Dept. Final '7.65-4040 ,
Water Engineering 765-5268
Sub LlsilBusiness License 765-519
Zoning 765-5139
Building Final (Lasllnspection. Only'
. After Above Complele)
Inspector
\
J{fPy
. .. PARTIAL.INSPECTIC>NS .
Build'.. ...e-..... .. ~... . . .... \ '..J?1..' :'
~l/-<>(,"-~ /~f>I Slr~ . WI' / .
. ~-'!..ov fjJ4a.... &"~ <;~
MechanicallnSDections
. .
. '.' ..... . ~ .... ~.~
Plumbi~ Insgection'1~ft1 v,f&.~.g'Se1!J' lbv .'
~. u, . ,,:; . I( rU"j Se. ~ ;9/ . eiJ~ foe. -.l-
C2r ....;;/1 d 4~o;P J...;.;" .
i~rJ-o)6,-"...,,;.k. T~;;II~
-;;'4!- ';?(~ -YLt"..,.-c..
Electrical'lnSDections /
;., .