910 S SHERRILL STCity of Anaheim
BUILDING DIVISION
INSPECTION RECORD
SWIMMING POOL
ADDRESS:
919 S SHERRILL ST
OWNER:
TEVES LEE
PERMIT#:
SW12021-00100
DATE ISSUED:
8/16/2021
DESCRIPTION:
New Pool/Spa: 300 sq ft gunite pool and 49 sq ft gunite spa.
POST THIS CARD WITH THE APPROVED PLANS IN A
CONSPICUOUS PLACE ON THE JOB SITE
Inspection
Code
Date
Inspect
1. Main Outlet.
2. Electric Bonding.
506
3. Steel.
508
4. Approval to Gunite.
510
l G
DO NOT GUNITE POOL/SPA
until all the above inspections have been signed.
5. Steel and bonding. 1
508
DO NOT GUNITE ROCK STRUCTURE
(water feature, rock slide, fountain, waterfall, grotto
etc.) until all the above inspections have been signed.
6. Underground elect.
5121
- -Z I
7. Gas piping test.
514
8. P-Trap Receptor.
516
9. Backflow Device.
518
10. Deck, Deck
Drains, & accessory
bonding.
520
(3 2
DO NOT POUR FLATWOR
until the above inspections have been signed.
11. Rough electric.
522
Zi-2
12. Fencing.
524
13. Plaster approval.
526
DO NOT PLASTER
until the above insqections have Oeen si ned.
14. Final Electric. 528 VW
Sub -Contractors list approved and
pool cover in place prior to final inspection.
15. FINAL
599
piy
MISC. INSPECTIONS
DATE
INSPECTOR
Inspectors can normally be reached between
7:30 - 8:00 A.M. and 3:30 - 4:30 P.M.
(714) 765-5153 + 0
Inspections 1 -5:
1. All plumbing to be complete and the system
pressurized to 35 lbs. with water or house pressure.
2. All metal within 5 feet of pool water, and all pool
equipment, must be bonded to pool reinforcing steel
with #8 solid copper wire. Niche light shell, deck
inserts, etc., shall be bonded to pool rebar.
3. Pool equipment is not required to be set at this fime.
Inspections 6 -10:
1. Underground electric inspected prior to backfilling.
2. Gas line test at 10# for 15 minutes, with 15# gauge.
3. When polyethylene gas piping is used, a certificate
from a certified installer and a metal tag at the meter
shall be provided per CPC 1211.3 APPENDIX I.
Inspections 11 -13:
1. Rough electric inspection when all wiring is
completed and ready to run prior to the plastering
of pool/spa.
2. City ordinance 6.56.010 requires that any pool, spa
or water feature containing water 18 inches or more
in depth shall be enclosed by a barrier adequate to
prevent entry of small children. The barrier shall
comply with Section 421 of the current CBC and City
of Anaheim ordinance 15.02.060.180 specifying the
height of any fence provided as barrier to the pool
shall be 60" above grade on the outside of the fence.
3. Doors from a garage shall meet the requirements
for a gate. Glass windows within 5' of pool water
shall be tempered glass.
4. Prior to pre -plaster inspection, streets, curbs and
city sidewalks will be inspected for any damage
due to construction of pool or spas.
5. Grading complete with positive drainage to street or
public way. All exposed plastic pipe painted to
protect from sunlight.
Inspections 14 -15:
1. After pool is operating and in working condition,
approved pool cover in place.
INSPECTION REQUESTS
Inspection requests made before 5:00 pm will be scheduled
on the following workday.
To schedule your building inspection online, please go to
htti)://www.anaheim.net/inspectionRequest.
You may also request your inspection by calling (714) 765.4626 and
continue with the following steps:
• Press 1 for inspection function.
• Press 1 to schedule inspection.
• Press 5 for Swimming Pool inspection.
• Enter your permit # 202100100.
• Enter the Code number for the inspection requested
(indicated in blue).
• Press 1 for next business day, or enter date preferred.
• Select time preference (Request is subject to
inspector's schedule.)
To access your inspection timeframe, please go to
www.anaheim.net/building after 7:30 am on the day of your
inspection. Under Online Services, click on the
"Inspection Timeframes" link or call (714) 765-5153 + 0.
swimcard